3 comments:

  1. who is providing the performance test?

    NEC230.95 (C) Performance Testing. The ground-fault protection
    system shall be performance tested when first installed on
    site. The test shall be conducted in accordance with instructions
    that shall be provided with the equipment. A written
    record of this test shall be made and shall be available to
    the authority having jurisdiction.

    ReplyDelete
    Replies
    1. "Groundfault
      protection of equipment shall be provided for solidly
      grounded wye electric services of more than 150 volts to
      ground but not exceeding 600 volts phase-to-phase for each
      service disconnect rated 1000 amperes or more."

      Our service is only 120 volts to ground therefore NEC230.95 does not apply!

      Delete
    2. You are correct!http://www.geindustrial.com/Newsletter/Spring05Ground.pdf, that spells it out in black and white, ground fault protection test is only needed on service
      voltage of 260-600volts.
      I showed the inspector this Letter and he agrees with us, but he is still going to look it up in the California 2010.

      Delete